Power-frequency magnetic field calculation around an indoor transformer substation

Author(s): A. Geri & G. M. Veca

Abstract:
The authors propose a full three-dimensional (3D) calculation model based on a multipole technique able to predict the magnetic field pollution outside of indoor medium voltage/low voltage (MV/LV) transformer substations.

The authors demonstrate that the proposed model may be advantageously used in all problems related to the characterization of the electromagnetic environment around a MV/LV transformer substation.

They also show how the model may be used to support the optimised design of the cabin layout when this solution is sufficient to assure the reduction (below the exposure limits fixed by law) of the magnetic flux density in target volumes within civil buildings.

In particular, the proposed algorithm has been applied to evaluate the magnetic flux density levels in the neighbourhood of a typical indoor MV/LV cabin placed at ground zero of a civil building (and therefore bordering on houses and/or offices).

In addition, in order to mitigate the magnetic field outside the transformer substation, using the proposed calculation code an attempt was made to design the layout of the cabin by rearranging the position of the LV distribution switchboard (i.e., the power center, PC).

Keywords:
magnetic pollution, magnetic field calculation, magnetic mitigation, MV/LV transformer substation, distribution power systems.

1 Introduction:
The installation of a new indoor MV/LV transformer substation (see fig.

1), in urban areas may be a very hard task with respect to the problems related to human exposure to power frequency magnetic fields.

In fact, these cabins are often placed in civil buildings therefore they border on houses or offices (i.e., places where people live for a large part of the day).

In addition, during the last ...

Pages: 10
Size: 342 kb
Paper DOI: 10.2495/BE050641

 

 

Download the Full Article

Price: US$ 0.00

This article is part of the WIT OpenView scheme and you can download the full text Adobe PDF article for FREE by clicking the 'Openview' icon below.

Send this page to a friend. Send this page to a colleague.



This paper can be found in the following book

Boundary Elements XXVII: Incorporating Electrical Engineering and Electromagnetics

Boundary Elements XXVII: Incorporating Electrical Engineering and Electromagnetics

Buy Book from
Witpress.com



Download the Full Article

This article is part of the WIT OpenView scheme and you can download the full text Adobe PDF article for FREE by clicking the 'Openview' icon to the right.


Copyright© 2006 by WIT Press | About Prof Carlos Brebbia
Optimised for Microsoft Internet Explorer